|
Some of the features
incorporated into our control system are:
- Auto Discharge Pressure
Setpoint
- Condenser Fan Sequencing
- Variable Speed Control
- Intelligent Condenser Pump
Control
- Non-Condensables Detection
- Defrost Pressure Increase
- Effective Condenser
Capacity Utilization

Auto Discharge
Pressure Setpoint
Ambient temperature and
relative humidity readings are used to calculate the wet bulb
temperature, the ideal limit for evaporative cooling, which is then
used to determine the discharge pressure setpoint. This setpoint is
constantly recalculated to utilize all the available condensing
capacity under the current ambient conditions. The minimum discharge
pressure setpoint is user adjustable.
Condenser Fan
Sequencing
Condenser fans sequence
on when the discharge pressure is above setpoint for a time delay
period, and sequence off when the pressure falls below setpoint.
Condenser fans will typically be set up so the fans will come on in
order of the smallest to largest. Under heavier load conditions this
order can be reversed, allowing the larger fans to come on first. When
two fans are of similar size, either one can be selected as the lead
fan.
|
|
|
|
Variable Speed Control
Condenser fans can be
operated over a range of 0 - 100% of full speed. This takes advantage
of the cubic fan law, which is that the power required to drive the fan
varies as the cube of the speed. In other words, the energy consumption
of the fan motor drops off dramatically as the speed is reduced. Refer
to the graph at the right for a better understanding of this fan power
curve.
Variable speed
technology is very well suited for condenser fans because all available
fans can run together at the same speed, thus utilizing the entire
surface area of the coils while dramatically reducing the power
consumption. The system uses intelligent control algorithms to operate
the fans at the speed required to match the refrigeration load,
eliminating the need to continually start/stop the motors to control
capacity.
The advantages
offered by variable speed control are as follows:
- maximum energy savings
- full time operation
of equipment resulting in uniform operating conditions
- reduced equipment wear
- reduced fan noise
|
|
 |
|
Condenser Pumps
The user enters the
start/stop pressures of each pump. Generally the pumps run all the
time, but in cold weather the pumps will sequence off when the
discharge pressure falls below the stop setpoints. When the pressure
rises again, the pumps will sequence back on according to their start
setpoints.
Non-Condensables
Non-condensables are
detected in the system by comparing the discharge pressure with the
pressure corresponding to the measured liquid condensate temperature. A
gauge on the condenser control screen displays the non-condensable
pressure to enable the user to know when purging is required.
|
|
|
|
A sample of one of
our condenser control screens from a freezer storage facility in
Woodland, Washington. This facility has two engine rooms, one of which
has 4 suction headers.
|
|
|
|
|